→VERTICALLY MOUNTED ONLY.
→INSTALL AS CLOSE TO THE COMPRESSOR AS POSSIBLE.
→SUCTION LINE FROM EVAPORATOR INTO INLET CONNECTION INSTALLED TO
SUCTION LINE OF COMPRESSOR.
→REVERSE CYCLE SYSTEMS REQUIRED. ACCUMULATOR TO BE INSTALLED
BETWEEN THE COMPRESSOR AND THE REVERSING VALVE.
→KEEP DIRECT FLAME AWAY FROM FUSIBLE RELIEF DEVICE WHILE
SOLDERING
CONNECTIONS.
→SAFE WORKING PRESSURE : 450PSI.
→MAXIMUM RECOMMENDED ACTUAL TONS BASED ON PRESSURE DROP THROUGH
ACCUMULATOR EQUIVALENT TO 1/2°F.
→MINIMUM EVAPORATOR TEMPERATURE -40°F. MINIMUM SUCTION GAS
TEMPERATURE THROUGH ACCUMULATOR +10°F.